Find Induced Voltage in Inductor
Given a Bushing Current Transformer (BCT) with a shorted secondary terminal. The BCT has 300 milliHenry (mH) rating and it has 0 to 200 mA current flowing through it every 2 microsecond. An electrical engineer remove the shorting wire on the BCT secondary terminal because he was told that the circuit was de-energized. Assuming there is a back feed circuit that energize the circuit at exact time the electrical engineer remove the shorting wire.
Calculate the induce voltage that the engineer will be exposed?
Important to remember: Do not remove the shorting wire on any ENERGIZED CT or BCT secondary terminal block because of very High Induced Voltage that can generate an ARC Flash Hazard.
The answer is valid if the units of measurement are in mH, mA, and microsecond. So you need to make measurement conversion to satisfy the calculator algorithm.
|
V | = |
mH * mA
microsecond
|